Foam fire extinguishing equipments and extinguishing agent

Closed Foam-Water Spray System

Main Technical Parameters

1. Operating pressure of proportioner: 0.6-1.2 MPa;

2. Specification of proportioner: PHY32, PHY48;

3. Flow rate of proportioner: 4-32L/s,4-48L/s;

4. Diameter of proportioner: DN65, DN80, DN100, DN150, DN200;

5. Mixing ratio: 3%-4% or 6%-7%;

6. Type of mixture: AFFF, FP/AR, FP;

7. Capacity of foam concentrate tank:

0.6, 0.8, 1.0, 1.5, 2.0, 3.0, 3.5, 4.0, 4.5, 5.0, 5.5, 7.6, 10.0m3(horizontal type) 

0.6, 0.8, 1.0, 1.5, 2.0, 3.0m3 (vertical type)


Description:

The closed foam-water spray system is a type of automatic water spray-foam combined fire extinguishing system. It is based on the original wet automatic water sprinkler fire extinguishing system to increase the foam supply device, the automatic sprinkler system and the low-expansion foam ratio mixing device (with capsule) are organically combined, and the water film is selected.It is a new and efficient fire extinguishing system combining foaming liquid and closed sprinklers.

This equipment is widely used in underground garages and places with more flammable liquids. Such as diesel engine room, oil refinery, oil tank farm, gas station, offshore oil production platform, oil boiler room, hangar, etc. The fire extinguishing system has the ability to quickly extinguish oil fires, has the advantages of high fire extinguishing efficiency, water saving, and low equipment investment and maintenance costs.

Executive standard: GB20031-2005 "General technical requirements for foam fire extinguishing system and components"


System Composition And Working Principle

1.System Composition


The closed foam-water spray system mainly consists of a fire pump set, a liquid supply device, a pressure-type proportional mixing device, an alarm valve device, a water flow indicator, a closed sprinkler, valves, pipes and accessories.


2.Working Principle


The working principle of the closed foam-water spray system (see figure): When the wet alarm valve is in the servo state, the whole system is filled with water at working pressure. Due to the function of the fixed ratio pressure reducing valve, the foam liquid storage tank provides The pressure of the foaming liquid is lower than the water pressure in the main network. At this time, the foaming liquid can fill the entire foaming liquid delivery pipeline to the entrance of the foaming proportional mixer, and due to the isolation effect of the one-way valve at the inlet of the mixer, The water in the pipe network cannot flow back into the foaming liquid pipeline. When the closed sprinkler in the protection zone explodes due to fire, the pressure on the wet alarm valve system side drops, the alarm valve opens, and the water flowing from the alarm port passes through the retarder and drives the hydraulic alarm to report glimpses. At the same time, the water flow opens the dual-purpose control valve (foaming liquid control valve) through the control pipeline, short-circuiting the pressure reducing valve, and the pressure in the foaming liquid storage tank rises, so that the pressure of the foaming liquid rises to the pressure in the main pipe. In the same way, the foam ratio mixing device flows to the nozzle according to a certain mixing ratio, and extinguishes the fire through the blasted nozzle.